Busbar Connection Terminals and Clamps

Screw terminals and plate clamps for tapping cables from 0.75 mm2 to 300 mm2 directly on 2T, 3T and TCC copper busbars.

  • Types: Screw terminals M5-M10, plate clamps
  • Conductor range: 0.75 - 300 mm²
  • Rated current: 360 A to 630 A (terminal dependent)
  • CT option: Class 1, 5 A secondary
Share to:

Description

Connection terminals are the interface between the copper bar and the cable. The CWNE range covers screw terminals for single cables and plate clamps where two cables land on the same point, all mounted directly on the bar without removing it.

Range

ParameterRange / value
Screw terminalsM5 x 8 (360 A), M5 x 12, M6 x 12, M8 x 12, M10 x 10 (630 A)
Clamp terminalsPlate clamps for 2T, 3T and TCC busbars
Conductor range0.75 mm² (18 AWG) to 300 mm² (600 MCM), copper
Cables per terminalOne cable per terminal as standard; plate clamps accept two
Tightening torqueStated per terminal, tolerance ±20 %
Current transformersBar-mounted CTs, class 1, 5 A secondary, 6.3 x 0.8 mm flat terminals to DIN 46 244-A

Installation

Remove oxide from the conductor before termination and apply contact protection; the conductor must be inserted far enough that the clamp closes on bare copper, with the insulation kept outside the terminal. Where two cables share a point, use a plate clamp rather than stacking lugs. Retighten after the first thermal cycle and at the recommended inspection interval.

Selection notes

  • Match the terminal current rating to the outgoing circuit, not to the busbar rating.
  • Check the conductor range: a terminal that is too large for the cable reduces the contact area and the current capacity.
  • Use a torque wrench — the stated torque must be held to ±20 % for the connection to stay stable.

Ordering information

State the busbar profile, the cable cross-section and number of cables per point, and the required terminal current.

FAQ

What cable sizes can be terminated on the busbar?

Copper conductors from 0.75 mm² (18 AWG) to 300 mm² (600 MCM), depending on the terminal selected.

Can two cables be connected at one point?

Yes, using a plate clamp. Stacking cable lugs under a single screw is not recommended.

Do you supply current transformers for the busbar?

Yes. Bar-mounted current transformers with class 1 accuracy, 5 A secondary and 6.3 x 0.8 mm flat terminals to DIN 46 244-A.

Why does the tightening torque matter?

The contact resistance and the thermal behaviour of the joint depend on the contact pressure. The stated torque must be held to plus or minus 20 percent, and the joint rechecked after the first thermal cycle.